CAD모델 선택
{thermokon/duct_sensors/climate_air_quality/akf10plus.prj},{NB=620864 AKF10+ NTC10k 050.06 (300)},{ARTNR=620864},{EL=50},{IDPIM3=1731},{BEZ=AKF10+ NTC10k 050.06},{GGEO=},{GEOV=},{REF3D=AKF10+ USE S},{BILD=akf10_plus_passiv_050.png},{INFOWWW=link zur Website},{MESSG= Temperatur},{AT= Kanal-/Tauchfühler},{BF=0},{BE=0},{KONFIG=---},{S= SI-Protection zum Schutz vor Feuchtigkeit und Vibrationen, NTC10k, passiv},{AGSPA=---},{AGST=---},{AGSK=---},{EG=0},{NTECH=---},{FTECH=0},{DUT=---},{TEB=-50 - +150},{GKT= ±0,22 K (typ. bei 25 °C), Potentiometer zur Offset-Einstellung},{TEB1=---},{AST=---},{TEBG=passiv -35..+90},{EBF= max. 85% rH nicht dauerhaft kondensierend},{EBD=0},{MBF=0},{GKF=0},{MBCO2=0},{GKCO2=0},{MVOCM=0},{MBL=0},{GKL=0},{MBAL=0},{LOD=300}
기술적 기준에 따라 원하는 제품을 선택하십시오. 선택할 수 있는 속성은 테이블 아이콘으로 표시됩니다. 선택은 테이블의 아이콘이나 값에 따라 재설정 됩니다.
HELP_VARIABLE
Naming
AKF10+ NTC10k 050.06
AKF10+ NTC10k 050.06
Article Number
620864
620864
Level of Detail
300
200
300
200
Picture
link to website
link to website
Measured values
temperature
Application/type
Duct/immersion sensor
Configuration
---
---
Sensor
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), NTC10k, passive
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), NTC10k, passive
Output voltage
---
---
Output current
---
---
Output switching contact
---
---
Network technology
---
---
Data transmission
---
---
Operating range temperature
-50 - +150
-50 - +150
Accuracy temperature
±0,22 K (typ. at 25 °C), potentiometer for offset adjustment
±0,22 K (typ. at 25 °C), potentiometer for offset adjustment
Operating range temperature enclosure
passive -35..+90
passive -35..+90
Operating range humidity
max. 85% rH short term condensation
Power supply
---
---
Power consumption
---
---
Material in touch with media
Sensor probe, Ø=6 mm, stainless steel V4A (1.4571), suitable for usage in aggressive media
Installation length
50
50
mm
Display
---
---
Enclosure
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC
Colour
pure white
pure white
Protection IP
IP65, according to EN 60529
Connection
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Connection cable
passive 2-wire
passive 2-wire
Mounting
when used as duct sensors: please use mounting flange MF6DS flexible (+90..+120 °C) or MF6 (brass, +120..+260 °C), or with enclosure USE-S with mounting clip, for use as immersion sensors please use immersion pocket THVADS / THMSDS
when used as duct sensors: please use mounting flange MF6DS flexible (+90..+120 °C) or MF6 (brass, +120..+260 °C), or with enclosure USE-S with mounting clip, for use as immersion sensors please use immersion pocket THVADS / THMSDS
Packaging
70 x 70 x 100
70 x 70 x 100
Delivery content
incl. mounting clip enclosure USE-S pure white, incl. mounting set (screws and accessories)
incl. mounting clip enclosure USE-S pure white, incl. mounting set (screws and accessories)
미리보기 - 생성
CAD
PDF
3D
2D