AKF10+ NTC10k 050.06
Article Number
620864
Level of Detail
Picture
akf10_plus_passiv_050.png
link to website
link to website
Measured values
temperature
Application/type
Duct/immersion sensor
Configuration
---
Sensor
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration), NTC10k, passive
Output voltage
---
Output current
---
Output switching contact
---
Network technology
---
Data transmission
---
Operating range temperature
-50 - +150
Accuracy temperature
±0,22 K (typ. at 25 °C), potentiometer for offset adjustment
Operating range temperature enclosure
passive -35..+90
Operating range humidity
max. 85% rH short term condensation
Power supply
---
Power consumption
---
Material in touch with media
Sensor probe, Ø=6 mm, stainless steel V4A (1.4571), suitable for usage in aggressive media
Installation length
50
mm
Display
---
Enclosure
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC
Colour
pure white
Protection IP
IP65, according to EN 60529
Connection
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Connection cable
passive 2-wire
Mounting
when used as duct sensors: please use mounting flange MF6DS flexible (+90..+120 °C) or MF6 (brass, +120..+260 °C), or with enclosure USE-S with mounting clip, for use as immersion sensors please use immersion pocket THVADS / THMSDS
Packaging
70 x 70 x 100
Delivery content
incl. mounting clip enclosure USE-S pure white, incl. mounting set (screws and accessories)