{thermokon/room_climate_control/room_sensors/climate_air_quality/ftb_plus_asmtab.prj},{NB=689083 FTB+ VV 66.06 L15m (300)},{ARTNR=689083},{EL=67},{IDPIM3=7169},{BEZ=FTB+ VV 66.06 L15m},{GGEO=},{GEOV=},{REF3D=FTB+ USE M},{BILD=ftb_plus.png},{INFOWWW=link zur Website},{MESSG= Temperatur, Feuchte},{AT= Wandfühler},{BF=0},{BE=0},{KONFIG= Thermokon App, uConfig, Jumper},{S=0},{AGSPA= 2x 0..10 V oder 0..5 V, einstellbar über Jumper, live-zero-Konfiguration über App oder uConfig, min. Last 10 kΩ},{AGST=---},{AGSK=---},{EG=0},{NTECH=---},{FTECH=0},{DUT=---},{TEB=-40 - +120},{GKT= ±0,3 K (typ. bei 21 °C), im Standardmessbereich, Potentiometer zur Offset-Einstellung, Offset-Einstellung über App oder uConfig},{TEB1=0},{LOD=300}
請根據技術需求選擇所需產品. 可選屬性在表格中高亮顯示. 選擇可以通過點擊表格或數值來重置.
HELP_VARIABLE
Naming
FTB+ VV 66.06 L15m
FTB+ VV 66.06 L15m
Article Number
689083
689083
Level of Detail
300
200
300
200
Picture
link to website
link to website
Measured values
temperature, humidity
Application/type
Wall sensor
Configuration
Thermokon app, uConfig, jumper
Output voltage
2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Output current
---
---
Operating range temperature
-40 - +120
Accuracy temperature
±0,3 K (typ. at 21 °C), within default measuring range, potentiometer for offset adjustment, offset setting via app or uConfig
Output signal temperature
scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transducer
Operating range temperature enclosure
-35..+70
Operating range humidity
max. 85% rH short term condensation
Measuring range humidity
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, adjustable at the transducer
Accuracy humidity
±2% between 10..90% rH (typ. at 21 °C), potentiometer for offset adjustment
Power supply
15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption
typ. 0,4 W (24 V =), 0,8 VA (24 V ~)
Material in touch with media
Sensor head, Ø=13 mm, end of sensor Ø=7 mm, stainless steel V2A (1.4305)
Installation length
67
67
mm
Enclosure
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour
pure white
Protection IP
enclosure IP65, according to EN 60529
Connection
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Connection cable
PVC, 0,14 mm², grey
length connection wire
15
Mounting
plastering or installation in hollow wall
Packaging
147 x 127 x 95
Delivery content
incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories)