CAD模型選擇
{thermokon/outdoor_sensors/climate_air_quality/la_plus_asmtab.prj},{NB=709934 LA+ CO2 LCD Temp_rH 3xV (300)},{ARTNR=709934},{EL=0},{IDPIM3=4978},{BEZ=LA+ CO2 LCD Temp_rH 3xV},{GGEO=},{GEOV=},{REF3D=LAplus USE M TrH},{BILD=la_plus_aq_lcd_temp_rh.png},{INFOWWW=link zur Website},{MESSG= Temperatur, Feuchte, CO2},{AT= Außenfühler},{BF=0},{BE=0},{KONFIG= Thermokon App, uConfig, Jumper},{S= NDIR (nicht dispersiv, infrarot)},{AGSPA= 3x 0..10 V oder 0..5 V, einstellbar über Jumper, live-zero-Konfiguration über App oder uConfig, min. Last 10 kΩ},{AGST=---},{AGSK=---},{EG=0},{NTECH=---},{FTECH=0},{DUT=---},{TEB=0 - +50},{GKT= ±0,5 K (typ. bei 21 °C), im Standardmessbereich, Offset-Einstellung über App oder uConfig},{TEB1=0},{LOD=300}
請根據技術需求選擇所需產品. 可選屬性在表格中高亮顯示. 選擇可以通過點擊表格或數值來重置.
HELP_VARIABLE
Naming
LA+ CO2 LCD Temp_rH 3xV
LA+ CO2 LCD Temp_rH 3xV
Article Number
709934
709934
Level of Detail
300
200
300
200
Picture
link to website
link to website
Measured values
temperature, humidity, CO2
temperature, humidity, CO2
Application/type
Outdoor sensor
Configuration
Thermokon app, uConfig, jumper
Thermokon app, uConfig, jumper
Sensor
NDIR (non-dispersive, infrared)
Output voltage
3x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
3x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Output current
---
---
Output switching contact
---
---
Network technology
---
---
Data transmission
---
---
Operating range temperature
0 - +50
Accuracy temperature
±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
Output signal temperature
scaling analogue output, 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
scaling analogue output, 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
Operating range humidity
max. 85% rH short term condensation
Measuring range humidity
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
Accuracy humidity
±2% between 10..90% rH (typ. at 21 °C)
±2% between 10..90% rH (typ. at 21 °C)
Measuring range CO2
0..2000, 0..5000, optionally configurable
0..2000, 0..5000, optionally configurable
Accuracy CO2
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Measuring VOC mixed gas
---
---
Power supply
15..35 V = SELV, 19..29 V ~ SELV
15..35 V = SELV, 19..29 V ~ SELV
Power consumption
max. 2,5 W (24 V =), 4,3 VA (24 V ~)
Material in touch with media
Pipe, PC, length 53 mm, with filter stainless steel wire mesh
Pipe, PC, length 53 mm, with filter stainless steel wire mesh
Display
LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, for example to display the air quality, optionally configurable via app or uConfig
LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, for example to display the air quality, optionally configurable via app or uConfig
Enclosure
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour
pure white, transparent cover
pure white, transparent cover
Protection IP
IP65, according to EN 60529
Connection
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Packaging
100 x 128 x 65
100 x 128 x 65
Delivery content
incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories)