CAD模型選擇
{thermokon/outdoor_sensors/climate_light/li65_plus_asmtab.prj},{NB=700696 Li65+ Temp_rH 3xV (300)},{ARTNR=700696},{EL=0},{IDPIM3=5017},{BEZ=Li65+ Temp_rH 3xV},{GGEO=},{GEOV=},{REF3D=AGS55+ USE M},{BILD=li65_plus.png},{INFOWWW=link zur Website},{MESSG= Temperatur, Feuchte, Helligkeit},{AT= Außenfühler},{BF=0},{BE=0},{KONFIG= Thermokon App, uConfig, Jumper, DIP-Schalter},{S= Umgebungslichtsensor mit präziser, dem menschlichen Auge entsprechender optischer Filterung},{AGSPA= 3x 0..10 V oder 0..5 V, einstellbar über Jumper, live-zero-Konfiguration über App oder uConfig, min. Last 10 kΩ},{AGST=---},{AGSK=---},{EG=0},{NTECH=---},{FTECH=0},{DUT=---},{TEB=-30 - +70},{LOD=300}
請根據技術需求選擇所需產品. 可選屬性在表格中高亮顯示. 選擇可以通過點擊表格或數值來重置.
HELP_VARIABLE
Naming
Li65+ Temp_rH 3xV
Li65+ Temp_rH 3xV
Article Number
700696
700696
Level of Detail
300
200
300
200
Picture
link to website
link to website
Measured values
temperature, humidity, luminosity
temperature, humidity, luminosity
Application/type
Outdoor sensor
Configuration
Thermokon app, uConfig, jumper, DIP switches
Thermokon app, uConfig, jumper, DIP switches
Sensor
ambient light sensor with precise optical filtering appropriate to the human eye
Output voltage
3x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
3x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Output current
---
---
Output switching contact
---
---
Network technology
---
---
Data transmission
---
---
Operating range temperature
-30 - +70
Accuracy temperature
±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
Output signal temperature
scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transducer, optionally configurable
scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transducer, optionally configurable
Operating range humidity
max. 85% rH short term condensation
Measuring range humidity
0..100% rH non-condensing
0..100% rH non-condensing
Accuracy humidity
±2% between 10..90% rH (typ. at 21 °C), offset setting via app or uConfig
±2% between 10..90% rH (typ. at 21 °C), offset setting via app or uConfig
Measuring range light
0..1000 lux (default setting), selectable from 6 ranges 0..200 lux | 0..1000 lux | 0..2 klux | 0..10 klux | 0..20 klux | 0..50 klux
Accuracy light
±5% of measuring range
Measuring range atm. pressure
---
---
Accuracy atmospheric pressure
---
---
Power supply
15..35 V = SELV, 19..29 V ~ SELV
15..35 V = SELV, 19..29 V ~ SELV
Power consumption
typ. 0,6 W (24 V =), 1,5 VA (24 V ~)
Enclosure
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour
pure white, translucent cover PC
Protection IP
IP65, according to EN 60529
Connection
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Packaging
128 x 100 x 65
Delivery content
incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories)
Preview - Generation