CAD model selection
Naming
MWF400+ LCD TRV MultiRange relay
Article Number
662963
Level of Detail
300
200
Picture
mwf400_plus_lcd.png
link to website
link to website
Measured values
temperature
Application/type
Duct averaging sensor
Configuration
Thermokon app, uConfig, jumper
Output voltage
0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Output current
---
Output switching contact
2x floating contact NO for 24 V ~ or 24 V = / 3 A
Network technology
---
Data transmission
---
Operating range temperature
-30 - +80
Accuracy temperature
±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
Output signal temperature
scaling analogue output, -20..+80 °C (default setting), selectable from 8 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable
Operating range temperature enclosure
LCD -20..+70
Operating range humidity
max. 85% rH short term condensation
Power supply
15..35 V = SELV, 19..29 V ~ SELV
Power consumption
max. 2,5 W (24 V =), 4,3 VA (24 V ~)
Material in touch with media
Sensor rod, copper, bendable, Ø=4 mm, Sensor neck, stainless steel V4A (1.4571), Ø=6 mm
Installation length
400 mm
Display
LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig
Enclosure
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour
pure white, transparent cover
Protection IP
IP65, according to EN 60529
Connection
removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², relay max. 1,5 mm²
Packaging
95 x 94 x 460
Delivery content
incl. mounting flange MF6DS flexible, incl. fixing kit rawlplugs and screws (2x each)
Preview - Generation
3D
2D