您可通過問題反饋或聯繫在線客服提交您的建議,我們將盡快完善:
Support
確定
??
不支持第三方 Cookie
您的瀏覽器不允許設置第三方 cookie。Please enable them in your browsers settings or click the button below.
請單擊此處在新選項卡中打開頁面內容。
If the opened page does not work initially, try reloading the page.
Please enable cookies in your browser for PARTcommunity to work
CAD模型選擇
{thermokon/room_climate_control/room_sensors/climate_air_quality/novos3.prj},{NB=735544 NOVOS 3 CO2+VOC Temp RS485 Modbus (300)},{ARTNR=735544},{EL=0},{IDPIM3=2634},{BEZ=NOVOS 3 CO2+VOC Temp RS485 Modbus},{GGEO=},{GEOV=},{REF3D=NOVOS 3 BIM},{COLOR=1.00,1.00,1.00,0.00},{BILD=novos_3_weiss.png},{INFOWWW=link zur Website},{MESSG= Temperatur, CO2, VOC},{AT= Raumfühler},{BF=0},{BE=0},{KONFIG= Thermokon App, uConfig, BUS, CO2+VOC jeder Ausgang kann über App oder uConfig für einen variablen Mix aus CO2 und VOC konfiguriert werden},{S=---},{AGSPA=---},{AGST=---},{AGSK=0},{EG=---},{NTECH= RS485 Modbus},{FTECH=0},{DUT=RS485 Modbus RTU, halbduplex, Baudrate 9.600, 19.200, 38.400 oder 57.600, Parität: keine (2 Stoppbits), gerade oder ungerade (1 Stoppbit)},{LOD=300}
請根據技術需求選擇所需產品. 可選屬性在表格中高亮顯示. 選擇可以通過點擊表格或數值來重置.
HELP_VARIABLE
Naming
NOVOS 3 CO2+VOC Temp RS485 Modbus
NOVOS 3 CO2+VOC Temp RS485 Modbus
Article Number
735544
735544
Level of Detail
300
200
300
200
Picture
link to website
link to website
Measured values
temperature, CO2, VOC
temperature, CO2, VOC
Application/type
Room sensor
Configuration
Thermokon app, uConfig, BUS, each output can be set to get a variable mix of CO2 and VOC by configuration via app or uConfig
Thermokon app, uConfig, BUS, each output can be set to get a variable mix of CO2 and VOC by configuration via app or uConfig
Sensor
---
---
Output voltage
---
---
Output current
---
---
Input
---
---
Network technology
RS485 Modbus
RS485 Modbus
Data transmission
RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit)
RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit)
Operating range temperature
0 - 50
Accuracy temperature
±0,5 K (typ. at 21 °C)
±0,5 K (typ. at 21 °C)
Output signal temperature
0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
Operating range humidity
max. 85% rH non-condensing
Measuring range humidity
---
---
Accuracy humidity
---
---
Measuring range CO2
0..2000, 0..5000, optionally configurable
0..2000, 0..5000, optionally configurable
Accuracy CO2
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Measuring VOC mixed gas
heated metal oxide semiconductor, self-calibration
heated metal oxide semiconductor, self-calibration
Power supply
15..35 V = SELV, 19..29 V ~ SELV
15..35 V = SELV, 19..29 V ~ SELV
Power consumption
typ. 0,4 W (24 V =), 0,8 VA (24 V ~)
typ. 0,4 W (24 V =), 0,8 VA (24 V ~)
Enclosure
NOVOS 3, PC V0
Colour
pure white
pure white
Protection IP
IP20
Connection
tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top)
Connection cable
---
---
Mounting
flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately
Packaging
115 x 105 x 30
Preview - Generation
CAD
PDF
3D
2D