CAD模型選擇
{thermokon/room_climate_control/room_sensors/climate_air_quality/novos5.prj},{NB=755634 NOVOS 5 CO2+VOC Temp Design LCD RS485 BACnet (MS/TP) (300)},{ARTNR=755634},{EL=0},{IDPIM3=1552},{BEZ=NOVOS 5 CO2+VOC Temp Design LCD RS485 BACnet (MS/TP)},{GGEO=},{GEOV=},{REF3D=NOVOS 5 BIM},{COLOR=0.31,0.31,0.31,0.00},{BILD=novos_5_co2_voc_weiss_design_schwarz_lcd.png},{INFOWWW=link zur Website},{MESSG= Temperatur, CO2, VOC},{AT= Raumfühler},{BF=0},{BE=0},{KONFIG= Thermokon App, uConfig, BUS},{S=0},{AGSPA=---},{AGST=---},{AGSK=0},{EG=0},{NTECH= RS485 BACnet (MS/TP)},{FTECH=0},{DUT=0},{TEB=0 - +50},{GKT= ±0,5 K (typ. bei 21 °C)},{TEB1=0},{AST=---},{TEBG=0},{EBF= max. 85% rH nicht kondensierend},{EBD=0},{MBF=---},{GKF=---},{LOD=300}
請根據技術需求選擇所需產品. 可選屬性在表格中高亮顯示. 選擇可以通過點擊表格或數值來重置.
HELP_VARIABLE
Naming
NOVOS 5 CO2+VOC Temp Design LCD RS485 BACnet (MS/TP)
NOVOS 5 CO2+VOC Temp Design LCD RS485 BACnet (MS/TP)
Article Number
755634
755634
Level of Detail
300
200
300
200
Picture
link to website
link to website
Measured values
temperature, CO2, VOC
temperature, CO2, VOC
Application/type
Room sensor
Room sensor
Configuration
Thermokon app, uConfig, BUS
Thermokon app, uConfig, BUS
Output voltage
---
---
Output current
---
---
Network technology
RS485 BACnet (MS/TP)
RS485 BACnet (MS/TP)
Operating range temperature
0 - +50
0 - +50
Accuracy temperature
±0,5 K (typ. at 21 °C)
±0,5 K (typ. at 21 °C)
Output signal temperature
---
---
Operating range humidity
max. 85% rH non-condensing
max. 85% rH non-condensing
Measuring range humidity
---
---
Accuracy humidity
---
---
Measuring range CO2
0..2000, 0..5000, optionally configurable
0..2000, 0..5000, optionally configurable
Accuracy CO2
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel
Measuring VOC mixed gas
heated metal oxide semiconductor, self-calibration
heated metal oxide semiconductor, self-calibration
Power supply
15..35 V = SELV, 19..29 V ~ SELV
15..35 V = SELV, 19..29 V ~ SELV
Display
LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, for example to display the air quality, optionally configurable via app or uConfig
LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, for example to display the air quality, optionally configurable via app or uConfig
Enclosure
NOVOS 5, PC V0
NOVOS 5, PC V0
Colour
pure white, with design cover alu or black, (please specify colour when ordering), (listed below)
pure white, with design cover alu or black, (please specify colour when ordering), (listed below)
Protection IP
IP30, according to EN 60529
IP30, according to EN 60529
Connection
tool-free mountable spring clamp, max. 1,5 mm²
tool-free mountable spring clamp, max. 1,5 mm²
Mounting
flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately
flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately
Packaging
170 x 110 x 45
170 x 110 x 45
Preview - Generation
CAD
PDF
3D