CAD模型選擇
{thermokon/room_climate_control/room_operating_units_controller/novos_touch.prj},{NB=735124 NOVOS Touch Temp_rH RS485 Modbus (300)},{ARTNR=735124},{EL=0},{IDPIM3=1442},{BEZ=NOVOS Touch Temp_rH RS485 Modbus},{GGEO=},{GEOV=},{REF3D=NOVOS Touch BIM},{COLOR=0.31,0.31,0.31,0.00},{BILD=novos_touch_weiss_schwarz.png},{INFOWWW=link zur Website},{MESSG= Temperatur, Feuchte},{AT= Raumbediengerät},{BF= Sollwertverstellung Temperatur, Lüfterstufenverstellung, Präsenzmeldung, Licht ein/aus/dimmen, Jalousie auf/ab/verstellen, Szenen aufrufen, ECO-Funktion, Messwertanzeige und -historie},{BE= Touchscreen},{KONFIG= Thermokon App, uConfig, BUS},{S=0},{AGSPA=0},{AGST=0},{AGSK=0},{EG= 1x Eingang für potentialfreien Kontakt},{NTECH= RS485 Modbus},{FTECH=0},{LOD=300}
請根據技術需求選擇所需產品. 可選屬性在表格中高亮顯示. 選擇可以通過點擊表格或數值來重置.
HELP_VARIABLE
Naming
NOVOS Touch Temp_rH RS485 Modbus
NOVOS Touch Temp_rH RS485 Modbus
Article Number
735124
735124
Level of Detail
300
200
300
200
Picture
link to website
link to website
Measured values
temperature, humidity
temperature, humidity
Application/type
Room operating unit
Operating functions
setpoint adjustment temperature, fan stage adjustment, presence detection, light ON/OFF/DIM, blind UP/DOWN/SET, setup scenarios, ECO function, showing measured value and history
Operating elements
touch screen
Configuration
Thermokon app, uConfig, BUS
Input
1x input for floating contact
Network technology
RS485 Modbus
Data transmission
RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit)
Operating range temperature
0 - +50
Accuracy temperature
±0,5 K (typ. at 21 °C), within default measuring range
Output signal temperature
0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
Operating range humidity
max. 85% rH non-condensing
Measuring range humidity
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
Accuracy humidity
±2% between 10..90% rH (typ. at 21 °C)
±2% between 10..90% rH (typ. at 21 °C)
Measuring range CO2
---
---
Accuracy CO2
---
---
Measuring VOC mixed gas
---
---
Power supply
24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption
typ. 2,5 W (24 V =), 5 VA (24 V ~)
Display
TFT 4,8", 1120x480 px, capacitive touch technology
Enclosure
NOVOS Touch, PC V0, cover glass, with thermal separation and sensor channel
Colour
pure white, with design cover NOVOS Touch glass black
Protection IP
IP30, according to EN 60529
Connection
tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top)
Mounting
flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately
Packaging
170 x 110 x 45