WK02+ ext. 24 V L4000
Article Number
763479
Level of Detail
300
200
Picture
link to website
link to website
Measured values
temperature, humidity, luminosity, conductivity
Application/type
Condensation sensor
Configuration
Thermokon app
Output voltage
2x 0..10 V or 0..5 V, adjustable via Thermokon app, live-zero configuration via app, min. load 10 kΩ
Output switching contact
changeover contact, 1 A resisitve load, max. 250 V, floating
Network technology
---
Data transmission
---
Operating range temperature
0 - +50
Accuracy temperature
±0,5 K (typ. at 21 °C)
Operating ranges temperature
0
Output signal temperature
scaling analogue output, 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable
Operating range humidity
max. 85% rH short term condensation
Measuring range humidity
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable
Accuracy humidity
±2% between 10..90% rH (typ. at 21 °C), potentiometer to adjust the sensitivity
Power supply
15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption
typ. 0,8 W (24 V =), 1,6 VA (24 V ~)
Installation length
73 mm
Display
LED green – power supply OK, LED red – condensation
Enclosure
USE-L, impact- and shock-resistant enclosure with quick-release cover, PC
Colour
pure white, transparent cover
Protection IP
IP65, according to EN 60529
Connection
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm²
Connection cable
PVC, 0,25 mm², white
length connection wire
4
Packaging
162 x 152 x 65
Delivery content
incl. mounting base enclosure USE-L pure white, incl. mounting set (screws and accessories), incl. cable tie 140x3,6 mm, incl. syringe thermal contact fluid 2 ml